CG170-12 Gas Generator Set
Gas Generator Sets
Details
Continuous Rating
1200 ekW @1.0pf
Fuel Type
Natural Gas, Biogas, Coal Gas
Maximum Electrical Efficiency
43.40%
Overview
1200 KW Gas & Coal Generator Set
From natural gas-fueled combined heat and power (CHP) systems and emergency power for facilities, to renewable biogas energy to support the local grid, or electricity generated from coal mine gases, Caterpillar has a wide range of reliable gas power solutions.
Benefits
Greater oil change interval
Lower lube oil consumption leading to greater time interval between lube oil changes
savings on service
Extended maintenance intervals leading to lower service costs
Lower lube oil consumption
leading to lower service costs and extended maintenance intervals
Features at a Glance
- High Efficiency, Lower Operating Costs
-
- Miller cycle timing with combustion chamber and spark plug improvement help on saving up to 15% fuel gas per year
- CG170 (non-miller) is optimized for Island-Mode capability
- Gearbox helps limit wear and tear on engine components, lowering operating costs and increasing availability
- Low installation, Building and Operating Costs
-
- Extended maintenance intervals up to 64,000 Oh
- Low fuel consumption due to improved combustion chamber and pre-chamber spark-plugs
- Flexible fields of application also with fluctuating gas qualities due to Total Electronic Management (TEM)
- Optimized oil management
- Optimized Lubrication Consumption
-
- Consumes up to 1900 liter less lube oil per year than comparable models<\li>
- Longer lubricant change and oil change intervals<\li>
Specifications
Full Specifications
- Generator Set Specifications
-
Continuous Rating
1200 ekW @1.0pfFuel Type
Natural Gas, Biogas, Coal GasMaximum Electrical Efficiency
43.40%Frequency
50 or 60 HzRPM
1500 rpm
- Engine Specifications
-
Engine Model
CG170-12Displacement
3240 in³Aspiration
TABore
6.7 inStroke
7.7 in
- Generator Set Dimensions
-
Length
235 inWidth
70 inHeight
87 inDry Weight - Genset
28659.8 lb
Equipment
- Standard Equipment
-
Air Inlet
- Turbocharger with a water-cooled bearing case for all cylinder
- One-element single-stage air cleaner with enclosure and sevice indicator
Control Panels
- TEM (Total Electronic Management)
Cooling
- Electrical jacket water and aftercooler coolant pump
- Jacket water and SCAC thermostats
- flange connections for JW inlet and outlet
Exhaust
- PEARL/Low resistence exhaust system
- Closed crankcase ventilation system
- Exhaust waste gate for the CG170-12
Fuel system
- Electronic fuel metering valve
- Independently controlled cylinder monitoring and ignition system
- Pre-chamber spark plugs
Generator
- Winding temperature detectors
- Reactive droop
- 3-phase sensing and KVAR/PF control
- Anti-condensation space heater
- closed-coupled generator result in no torque transmission to the base frame
- Busbar connections
- grid code generator
Starting/Charging
- 24V starting motors
- Battery disconnect switch
General
- Crankshaft vibration damper and guard
- Optional Equipment
-
Cooling
- CHP skid
Grid Code Compliance
- 50Hz: Germany, Belgium, Great Britain, Italy, Poland, and Netherlands