DE400S GC Generator Set

Diesel Generator Sets

Details

Standby Rating
400 ekW

Frequency
60 Hz

Emissions/Fuel Strategy
Low BSFC

Contact

Foley Equipment Sales

+1 (316) 943-4211

Request a Quote

Overview

400 ekW Diesel Generator Set

The DE400S GC diesel generator sets have been developed for your standby applications. Producing reliable power of 400 ekW at 60 Hz, our C9.3 diesel-powered DE400S GC generator set is designed to ISO 8528-5 transient response requirements

Benefits

Control System

  • Track Genset Health and Operation Parameters
  • Genset Utilization and Performance Tracking

Monitoring

Cat Connect option ensures your generator set is always ready to start and perform as expected

Consumption

Features at a Glance

Cat Generator Set Package
        
  • Cat generator set packages have been fully prototype tested
  •     
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  •     
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
        
  • Reliable, rugged, durable design
  •     
  • Field-proven in thousands of applications worldwide
  •     
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
        
  • Superior motor starting capability minimizes need for oversizing alternator
  •     
  • Designed to match performance and output characteristics of Cat diesel engines
  •     
  • Robust Class H insulation
GCCP 1.1 Control Panel
        
  • User-friendly interface and navigation
  •     
  • Scalable system to meet a wide range of installation requirement
  •     
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
        
  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  •     
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
One Safe Source
        
  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  •     
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  •     
  • Each generator set package is tested before leaving the Caterpillar facility
  •     
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
        
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  •     
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Specifications

Full Specifications

Generator Set Specifications

Standby Rating
400 ekW

Frequency
60 Hz

Emissions/Fuel Strategy
Low BSFC

Voltage
220 to 480 Volts

Speed
1800 rpm

Duty Cycle
Standby

Engine Specifications

Engine Model
C9.3B ATAAC, I-6, 4-Stroke Water-Cooled Diesel

Bore
4.53 in

Stroke
5.87 in

Displacement
567.5 in³

Compression Ratio
16.5:1

Aspiration
Air to Air Aftercooled

Fuel System
Direct Injection

Governor Type
Adem™A4

Generator Set Dimensions

Length - Maximum
186.7 in

Width - Maximum
79.3 in

Height - Maximum
84 in

Equipment

Standard Equipment

Engine

  • C9.3B, Inline 6 cylinder, 4 stroke diesel

Genset Control

  • GCCP 1.1

Governor

  • Adem A4

Alternator

  • A Frame standard alternator

Fuel Storage

  • Single wall 8 hour fuel tank

Air, Cooling & Exhaust

  • Standard air filter

General

  • Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment

European Certificates

  • Australia, CIS, Gulf Certification
  • EU Certificate of Conformance (CE)

Auxiliary Supply Voltage

  • 240V

Alternator Requirements

  • Space heater
  • IP Standard @ 21 FUW A-Frame

Fuel Storage

  • High fuel level alarm
  • Dual wall 8 hour fuel tank
  • Single wall tank with containment 01
  • Fuel level sender
  • Low fuel level shutdown
  • Low fuel level alarm

Enclosure

  • Cat GC enclosure

Genset Control

  • Speed adjust potentiometer
  • Battery charger
  • Standby Pack (Smart Jacket water heater, Battery charger)
  • Voltage adjust potentiometer
  • PLG Cellular 4G E
  • Low coolant temperature alarm
  • Battery
  • Oil temperature displays
  • PLG Cellular 4G U
  • Coolant heater
  • PLG Ethernet

Circuit breaker

  • Overload via alarm switch on breaker
  • 3 Pole Circuit breaker 1250A
  • Neutral earth link
  • 4 Pole Circuit breaker 630A
  • 4 Pole Circuit breaker 1250A
  • 4 Pole Circuit breaker 800A
  • Circuit breaker padlock
  • Auxiliary contacts
  • 3 Pole Circuit breaker 800A
  • Shunt Trip
  • 3 Pole Circuit breaker 630A

Air, Cooling & Exhaust

  • 6" Elbow kit
  • 6" Elbow kit
  • 5" Elbow kit
  • 5-6" Exhaust adapter
  • Canopy silencer
  • 6" Muffler - 25 dBA attenuation
  • Dual element air filter
  • Single stage air filter
  • No muffler
  • 5" Muffler - 10 dBA Attenuation

Similar New Power Solutions

C1.1 Generator Set
Diesel Generator Sets

C1.1 Generator Set

Standby Rating: 7.5/9.5 kVA
Prime Power Rating: 6.8/8.5 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C1.5 Generator Set
Diesel Generator Sets

C1.5 Generator Set

Standby Rating: 11/12/13.5/16 kVA
Prime Power Rating: 10/11/12.5/14.5 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C3.3 Generator Set
Diesel Generator Sets

C3.3 Generator Set

Standby Rating: 26/33/40/50 kVA
Prime Power Rating: 24/30/36/45 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage II / EU Stage IIIA

C2.2 Generator Set
Diesel Generator Sets

C2.2 Generator Set

Standby Rating: 14/16.5/18/22 kVA
Prime Power Rating: 13/15/16.5/20 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C4.4 Generator Set
Diesel Generator Sets

C4.4 Generator Set

Standby Rating: 55/65/88/90/110 kVA
Prime Power Rating: 50/60/80/82/100 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage IIA / EU Stage IIIA

C7.1 ACERT
Diesel Generator Sets

C7.1 ACERT

Standby Rating: 150/165/175/200/220 kVA
Prime Power Rating: 135/150/160/180/200 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage IIIA

3512B Diesel Generator Set
Diesel Generator Sets

3512B Diesel Generator Set

Standby Rating: 1625/1600/1500 kVA
Prime Power Rating: 1500/1360 kVA
Emissions/Fuel Strategy: Low Fuel , Low Emissions

3512 Generator Set
Diesel Generator Sets

3512 Generator Set

Standby Rating: 1400/1250 kVA
Prime Power Rating: 1275/1150 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516B Generator Set
Diesel Generator Sets

3516B Generator Set

Standby Rating: 2250 kVA
Prime Power Rating: 2000 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516 Diesel Generator Set
Diesel Generator Sets

3516 Diesel Generator Set

Standby Rating: 2000 kVA
Prime Power Rating: 1825 kVA
Emissions/Fuel Strategy: Low Fuel Consumption