C13 Generator Set

Diesel Generator Sets

Details

Standby Rating
400/450 kVA

Prime Power Rating
350/400 kVA

Emissions/Fuel Strategy
Low BSFC

Contact

Foley Equipment Sales

+1 (316) 943-4211

Request a Quote

Overview

350 - 450 kVA Diesel Generator Set

The C13 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 350 to 450 kVA at 50 Hz, our C13 diesel generator sets designed to ISO 8528-5 transient response requirements. These generator sets range from low fuel consumption systems EU Stage IIIA Non-road Emission Standards Emissions / Fuel Strategy.

Benefits

Control System

  • Track Genset Health and Operation Parameters
  • Genset Utilization and Performance Tracking

Monitoring

Cat Connect option ensures your generator set is always ready to start and perform as expected

Lower Fuel Consumption

Longer run times between fuel fills; reduced operating costs

Features at a Glance

Cat Generator Set Package
        
  • Cat generator set packages have been fully prototype tested
  •     
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  •     
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
        
  • Reliable, rugged, durable design
  •     
  • Field-proven in thousands of applications worldwide
  •     
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
        
  • Superior motor starting capability minimizes need for oversizing alternator
  •     
  • Designed to match performance and output characteristics of Cat diesel engines
  •     
  • Robust Class H insulation
GCCP 1.3 Control Panel
        
  • User-friendly interface and navigation
  •     
  • Scalable system to meet a wide range of installation requirement
  •     
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
        
  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  •     
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
One Safe Source
        
  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  •     
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  •     
  • Each generator set package is tested before leaving the Caterpillar facility
  •     
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
        
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  •     
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Specifications

Full Specifications

Generator Set Specifications

Standby Rating
400/450 kVA

Prime Power Rating
350/400 kVA

Emissions/Fuel Strategy
Low BSFC

Voltage
380 to 415 Volts

Frequency
50 Hz

Speed
1500 rpm

Duty Cycle
Standby, Prime

Engine Specifications

Engine Model
C13 ATAAC, I-6, 4-Stroke Water-Cooled Diesel

Bore
5.12 in

Stroke
6.18 in

Displacement
762.8 in³

Compression Ratio
16.3:1

Aspiration
Air to Air Aftercooled

Fuel System
MEUI

Governor Type
Adem™A4

Generator Set Dimensions

Length - Maximum
186.7 in

Width - Maximum
79.3 in

Height - Maximum
84 in

Equipment

Standard Equipment

Air Inlet System

  • Turbocharger
  • Aftercooler core
  • Air cleaner; light duty with disposable paper filter

Control Panel

  • GCCP 1.3

Cooling System

  • Radiator and cooling fan with guard
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive
  • Coolant drain line with valve

Exhaust System

  • Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose

Fuel System

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied

Generator and Attachments

  • Power center, IP22
  • Segregated low voltage (AC/DC) wiring panel
  • Optional LC Frame generator - IP23 Protection
  • Integrated voltage regulator (IVR)
  • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • A Frame generator - IP21 Protection

Packaged Generator Set

  • Coolant drain line with valve
  • Disposable air filter
  • Coolant level sight gauge
  • Low coolant level sensor
  • Radiator package mounted
  • Service indicator

Governing System

  • Cat electronic governor (ADEM A4)

Lube System

  • Oil drain valves
  • Lubricating oil
  • Oil cooler

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant and lube oil drain lines

Starting / Charging System

  • 24V battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment

European Certificates

  • Global Certification for CIS
  • EU Certificate of Conformance (CE)

Air Inlet System

  • Dual element air cleaner
  • Single element air cleaner

Circuit breakers

  • Power terminal strip
  • 3 Pole (IEC-100% rated) Circuit breakers - Motorised
  • Circuit breaker (IEC) Auxiliary contacts
  • 4 Pole (IEC-100% rated) Circuit breaker - Motorised
  • Padlockable circuit breaker device
  • Shunt trip for IEC circuit breaker
  • 3 Pole (IEC-100% rated) Circuit breaker
  • 4 Pole (IEC-100% rated) Circuit breaker

Control Panels

  • GCCP 1.4
  • Volt free contacts
  • Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
  • Local alarm modules: Local annunciator
  • Remote annunciator module

Cooling System

  • Stone guards
  • Radiator duct flange
  • Low coolant temperature alarm

Enclosures

  • High ambient sound attenuated enclosures
  • Sound attenuated enclosures

Exhaust System

  • 10, 25 and 35 dBA attenuation
  • Mufflers - End in/end out
  • 6 and 8 inch flange GP
  • 6 and 8 inch elbow kit
  • Flexible 8 inch exhaust fittings

Fuel System

  • Manual fuel transfer pump
  • Optional BS799 Compliant Integral dual wall fuel tank base
  • Fuel transfer system controls

Generator and Attachments

  • A Frame oversize generator
  • Permanent magnet excitation (PMG) generator
  • Ingress protection
  • A Frame CIP generator
  • LC frame generator
  • LC CIP generator
  • Space heaters

Lube System

  • Manual sump pump

Mounting System

  • Narrow skid base

starting / Charging System

  • Battery disconnect switch
  • 5 Amp single Battery charger
  • Jacket water heater

Similar New Power Solutions

C1.1 Generator Set
Diesel Generator Sets

C1.1 Generator Set

Standby Rating: 7.5/9.5 kVA
Prime Power Rating: 6.8/8.5 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C1.5 Generator Set
Diesel Generator Sets

C1.5 Generator Set

Standby Rating: 11/12/13.5/16 kVA
Prime Power Rating: 10/11/12.5/14.5 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C3.3 Generator Set
Diesel Generator Sets

C3.3 Generator Set

Standby Rating: 26/33/40/50 kVA
Prime Power Rating: 24/30/36/45 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage II / EU Stage IIIA

C2.2 Generator Set
Diesel Generator Sets

C2.2 Generator Set

Standby Rating: 14/16.5/18/22 kVA
Prime Power Rating: 13/15/16.5/20 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C4.4 Generator Set
Diesel Generator Sets

C4.4 Generator Set

Standby Rating: 55/65/88/90/110 kVA
Prime Power Rating: 50/60/80/82/100 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage IIA / EU Stage IIIA

C7.1 ACERT
Diesel Generator Sets

C7.1 ACERT

Standby Rating: 150/165/175/200/220 kVA
Prime Power Rating: 135/150/160/180/200 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage IIIA

3512B Diesel Generator Set
Diesel Generator Sets

3512B Diesel Generator Set

Standby Rating: 1625/1600/1500 kVA
Prime Power Rating: 1500/1360 kVA
Emissions/Fuel Strategy: Low Fuel , Low Emissions

3512 Generator Set
Diesel Generator Sets

3512 Generator Set

Standby Rating: 1400/1250 kVA
Prime Power Rating: 1275/1150 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516B Generator Set
Diesel Generator Sets

3516B Generator Set

Standby Rating: 2250 kVA
Prime Power Rating: 2000 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516 Diesel Generator Set
Diesel Generator Sets

3516 Diesel Generator Set

Standby Rating: 2000 kVA
Prime Power Rating: 1825 kVA
Emissions/Fuel Strategy: Low Fuel Consumption