3516C Generator Set

Diesel Generator Sets

Details

Standby Rating
2750 kVA

Prime Power Rating
2500 kVA

Emissions/Fuel Strategy
Low Fuel, Low Emissions

Contact

Foley Equipment Sales

+1 (316) 943-4211

Request a Quote

Overview

2500 - 2750 kVA Diesel Generator Set

Producing reliable power from 2275 to 2750 kVA at 50 Hz, our 3516C diesel generator sets are made to meet your mission critical, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. The generator set offers both low fuel consumption and low emission systems.

Benefits

Global Operating Hours

Proven performance in heavy-duty applications

Shipped

Since 1981, leading the large engine market

Lower Fuel Consumption

Demonstrated savings in operating costs

Features at a Glance

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
Cat ECS Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
        
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  •     
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • IBC seismic certification
  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)
One Safe Source
  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Specifications

Full Specifications

Generator Set Specifications

Standby Rating
2750 kVA

Prime Power Rating
2500 kVA

Emissions/Fuel Strategy
Low Fuel, Low Emissions

Voltage
380 to 11000 volts

Frequency
50 Hz

Speed
1500 rpm

Duty Cycle
Standby, Mission Critical, Prime, Continuous

Maximum Rating
2750 kVA

Minimum Rating
2500 kVA

Engine Specifications

Engine Model
3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel

Bore
6.69 in

Stroke
8.46 in

Displacement
4764.73 in

Compression Ratio
14.7:1

Aspiration
TA

Fuel System
Electronic unit injection

Governor Type
Adem™3

Generator Set Dimensions

Length - Maximum
276.3 in

Width - Maximum
92.1 in

Height - Maximum
118.2 in

Dry Weight - Genset (maximum)
39090 lb

Equipment

Standard Equipment

Air Inlet

  • Air cleaner

Cooling

  • Package mounted radiator

Exhaust

  • Exhaust flange outlet

Fuel

  • Fuel priming pump
  • Secondary fuel filters
  • Primary fuel filter with integral water separator

Generator

  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection

Power Termination

  • Busbar

Control Panel

  • Cat ECS 100

General

  • Paint - Caterpillar yellow except rails and radiators gloss black
Optional Equipment

Exhaust

  • Exhaust mufflers

Generator

  • Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
  • Anti-condensation heater
  • Oversize and premium generators

Power Termination

  • Circuit breakers, IEC compliant
  • Circuit breakers, UL listed

Control Panels

  • EMCP 4.4
  • Digital I/O module
  • Load share module
  • Generator temperature monitoring & protection
  • Remote monitoring software

Mounting

  • Spring type vibration isolators
  • Rubber anti-vibration mounts
  • IBC isolators

Starting/Charging

  • Jacket water heater
  • Charging alternator
  • Oversize batteries
  • Battery chargers
  • Heavy duty starting system
  • Air starting motor with control and silencer

General

  • UL 2200 package
  • EU Certificate of Conformance (CE)
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • EEC Declaration of Conformity
  • Integral & sub-base UL listed dual wall fuel tanks
  • The following options are based on regional and product configuration:
  • Automatic transfer switches (ATS)
  • Enclosures: Sound attenuated, weather protective
  • CSA Certification
  • Integral & sub-base fuel tanks

Similar New Power Solutions

C1.1 Generator Set
Diesel Generator Sets

C1.1 Generator Set

Standby Rating: 7.5/9.5 kVA
Prime Power Rating: 6.8/8.5 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C1.5 Generator Set
Diesel Generator Sets

C1.5 Generator Set

Standby Rating: 11/12/13.5/16 kVA
Prime Power Rating: 10/11/12.5/14.5 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C3.3 Generator Set
Diesel Generator Sets

C3.3 Generator Set

Standby Rating: 26/33/40/50 kVA
Prime Power Rating: 24/30/36/45 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage II / EU Stage IIIA

C2.2 Generator Set
Diesel Generator Sets

C2.2 Generator Set

Standby Rating: 14/16.5/18/22 kVA
Prime Power Rating: 13/15/16.5/20 kVA
Emissions/Fuel Strategy: EU Stage IIIA

C4.4 Generator Set
Diesel Generator Sets

C4.4 Generator Set

Standby Rating: 55/65/88/90/110 kVA
Prime Power Rating: 50/60/80/82/100 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage IIA / EU Stage IIIA

C7.1 ACERT
Diesel Generator Sets

C7.1 ACERT

Standby Rating: 150/165/175/200/220 kVA
Prime Power Rating: 135/150/160/180/200 kVA
Emissions/Fuel Strategy: Low BSFC / EU Stage IIIA

3512B Diesel Generator Set
Diesel Generator Sets

3512B Diesel Generator Set

Standby Rating: 1625/1600/1500 kVA
Prime Power Rating: 1500/1360 kVA
Emissions/Fuel Strategy: Low Fuel , Low Emissions

3512 Generator Set
Diesel Generator Sets

3512 Generator Set

Standby Rating: 1400/1250 kVA
Prime Power Rating: 1275/1150 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516B Generator Set
Diesel Generator Sets

3516B Generator Set

Standby Rating: 2250 kVA
Prime Power Rating: 2000 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516 Diesel Generator Set
Diesel Generator Sets

3516 Diesel Generator Set

Standby Rating: 2000 kVA
Prime Power Rating: 1825 kVA
Emissions/Fuel Strategy: Low Fuel Consumption