Cat® CG – ATS for general purpose applications
ATS TruOne - TruControl
Details
Rating Range
30 - 3000 A
Transfer Type
Open Transition (CG), Delayed Transition (CGD)
Switch Type
Contactor
Overview
Cat® CG Series
The CG Series – Contactor-type, Open Transition (CG) and Delayed Transition (CGD) ATS for general purpose applications offers functionality for critical emergency power applications in commercial and light industrial applications, with an enhanced feature set and LCD HMI interface.
The CG provides a durable mechanism that is tested up to 6,000 cycles. Electrical system parameters are set via the HMI and pre-configuration file upload is available via USB or Bluetooth connection.
Benefits
CG LCD HMI
Voltage and frequency sensing of both sources and load
Available Bluetooth connection and enhanced communication capabilities
Features at a Glance
- Product Features
-
- Voltage and frequency sensing of both sources and load
- USB port to upload/download settings
- Available Bluetooth connection and enhanced communication capabilities
- Password protection LCD HMI
- Integrated help button and menu
- Automatic Configuration Function
- Control Panel
-
- TruOne L3 - CG LCD HMI to set electrical system parameters with file upload via USB or Bluetooth connection.
- Functions
-
- Provision of transfer & re-transfer control signals
- Provision of engine/generator start and shutdown signals
- Permit user programming of set points
- Display real time and historical information
- Permit system testing
- Store all parameters in nonvolatile memory
- Standards
-
- UL 1008, NFPA 70, 99, 101 and 110
- NEMA ICS 10
- cUL
Specifications
Full Specifications
- Technical Summary
-
Rating Range
30 - 3000 ATransfer Type
Open Transition (CG), Delayed Transition (CGD)Switch Type
Contactor
- System Information
-
Product nodes
30, 60, 100, 125, 160, 200, 260, 400, 600, 800, 1000, 1200, 1600, 2000, 2600, 3000ARated Voltage and Frequency
200-480VAC, 50/60 HzPhase system
Single and Three (three phase only >600A)Number of poles
2, 3 and 4 (3 & 4 pole only >600A)Neutral configuration
Optional Solid or Switched neutralProduct type
Open transition (I-II), Delayed Transition (I-O-II)
Equipment
- Standard Equipment
-
Control
- LCD + keys
- Voltage and frequency settings: Pick up and Drop out
- Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF, Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead
- Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence
Additional Features
- LED indications for ATS, S1 and S2 status
- Open transition - Standard digital inputs/outputs (1/1)
- Delayed transition - Standard digital inputs/outputs (2/1)
- Programmable digital inputs/outputs
- Auto config (voltage, frequency, phase system)
- Source priority (Source 1/2, No priority)
- Manual re-transfer
- In-phase monitor (synchro check)
- Genset exercising: on-load, off-load
- Load shedding
- Real time clock
- Event log
- Optional Equipment
-
Accessories
- Auxiliary contacts for position indication
- Additional digital input/output contacts (adding up to 6 each)
- 12-24 VDC aux supply module for controller
- Communication modules
Connectivity Capability
- Modbus RTU (RS-485)
- Modbus/TCP
- Profibus DP
- ProfiNet Yes
- DeviceNet
- Ethernet IP